Sound insulation in modular duplexes and townhouses

This page describes the NCC 2022 Housing Provisions as published by the Australian Building Codes Board. States and territories can vary the code, and the building surveyor or certifier decides what applies to a specific project. Nothing here is compliance advice.
Separating walls at a glance
Where it appliesWalls between attached Class 1 buildings, and between a Class 1 building and an unrelated Class 10a building[1]
Airborne ratingRw + Ctr of not less than 50[1]
Wet roomsDiscontinuous construction where a bathroom, toilet, laundry or kitchen adjoins a habitable room next door[1]
FloorsNo floor requirement appears in the Part 10.7 text read for this page[1]
Northern TerritoryReplacement text uses a different measure: DnT,w + Ctr of not less than 45[2]

A duplex or townhouse built from factory-made modules is, for code purposes, usually two attached houses rather than an apartment building, and the National Construction Code (NCC) treats the shared wall as a sound barrier in its own right. This page sets out what the NCC 2022 says about that wall. For how the classes are decided see building classes for shared housing; for pricing see modular duplex costs.

Where the rules sit §

Attached dwellings separated by a fire-resisting wall are Class 1a under the NCC, so they fall in Volume Two, the volume for houses.[1] The Volume Two performance requirement for sound is H4P6, which asks for insulation sufficient to prevent illness or loss of amenity; the base text gives no number. Following Part 10.7 of the Housing Provisions is the deemed-to-satisfy way of meeting it.[2]

ItemRequirementSource
Airborne sound, wallRw + Ctr of at least 50Housing Provisions 10.7[1]
Wet room next to habitable roomDiscontinuous constructionHousing Provisions 10.7[1]
Wall heightTo roof underside or insulating ceilingHousing Provisions 10.7[1]
Floors, impact ratingNo figure in text readHousing Provisions 10.7[1]

Rw + Ctr is a laboratory-style rating of how much airborne sound a wall construction blocks, adjusted to count low-frequency noise such as bass and traffic. A higher number means less sound passes through. The figure of 50 applies to separating walls between Class 1 buildings, and between a Class 1 building and an unrelated Class 10a building such as a neighbouring garage.[1]

Wet rooms and discontinuous construction §

Where a bathroom, toilet, laundry or kitchen in one dwelling sits against a habitable room (other than a kitchen) in the next, the wall must be discontinuous.[1] Discontinuous construction means the two sides are separate leaves that do not share framing, so vibration does not pass straight across. The text read does not give an impact-sound number for this situation.[1]

How compliance is shown §

A wall can show its Rw + Ctr by laboratory measurement under AS/NZS ISO 717.1, by using one of the deemed-to-satisfy constructions in the code, or by a proprietary system tested to the same standard.[1] The listed constructions cover masonry, concrete, autoclaved aerated concrete, and two-row timber or steel stud walls with an air gap between the rows.[1] Because these listed walls are described in terms of site-built materials, whether a particular module wall system matches one of them, or relies on tested data, is a matter for its documentation and the certifier. This page does not cover any specific system.

Details that affect the result §

Part 10.7 also sets out how a wall is built. Junctions with perimeter walls and roof cladding are sealed, plasterboard joints are staggered and taped where two layers are used, and steel and timber framing have stated details, such as noggings that do not bridge studs supporting different leaves.[1] These matter in modular building because a duplex of two sets of modules has a joint line exactly where the separating wall sits; the code text read does not address that joint specifically.

Services are treated separately. Services cannot be chased into masonry or concrete separating walls, access panels for pipes in the wall must not open into a habitable room other than a kitchen, water pipes must sit in discontinuous construction, and power outlets on opposite sides are offset by at least 100 mm in masonry or 300 mm in timber or steel-framed walls.[1]

State variations §

The Northern Territory has replacement text for this requirement. It measures the wall by in-situ DnT,w + Ctr, with a minimum of 45, rather than by the Rw + Ctr 50 laboratory rating in the Housing Provisions.[2] The two figures are on different measuring bases and are not interchangeable. How other states and territories adopt or vary this part of the code is not covered by sources compiled here.

What is not covered here §

Floor-to-ceiling sound insulation for stacked dwellings (Class 2 apartments) is outside this page; it deals with side-by-side attached houses only. The Housing Provisions text read gives no impact-sound figure and no floor requirement for Class 1 dwellings, and this page does not infer one.

The deemed-to-satisfy wall build-ups in detail, NCC 2025 changes, state and territory variations other than the Northern Territory, the acoustic performance of any modular builder's separating wall, costs of acoustic upgrades, and whether sound testing is required on completion are not covered by sources compiled here. Local planning conditions and covenants are also outside scope.

Compliance for a specific building is determined by the building surveyor or certifier.

Ask Modular Living AI about this guide

Still have a question after reading this guide? Ask it here. The answer draws on this guide, our other guides and the official pages they cite, with links to each one it used.

General information only, not legal, financial or building advice.

The Dispatch — a monthly email when new guides are published. No noise; unsubscribe anytime.

Sent to info@modularlivingaustralia.com.au and handled by a person. See Privacy.

References §

  1. Australian Building Codes Board — NCC 2022 Housing Provisions, Part 10.7 Sound insulation — Applies to separating walls between Class 1 buildings and between a Class 1 and an unrelated Class 10a building. Airborne requirement Rw + Ctr not less than 50. Discontinuous construction where a bathroom, sanitary compartment, laundry or kitchen adjoins a habitable room (other than a kitchen) in the adjoining building. Wall must continue to the underside of the roof or to a ceiling giving the required insulation. Rw + Ctr may be established by laboratory measurement to AS/NZS ISO 717.1 or by listed deemed-to-satisfy wall constructions (masonry, concrete, autoclaved aerated concrete, and timber or steel framing). Construction rules cover sealing of junctions, plasterboard joints, steel and timber framing details. Services rules cover not chasing services into masonry or concrete walls, access panels, water pipes and offset electrical outlets. Explanatory note: requirements apply to wall parts common to adjoining Class 1 buildings but not to wall parts in the subfloor. No impact rating figure appears in the text. nccb.gov.au/editions/ncc-2022/adopted/housing-provisions/10-health-and-amenity/part-107-sound-insulation
  2. Australian Building Codes Board — NCC 2022 Volume Two, Part H4 Health and amenity (Northern Territory variation) — Performance Requirement H4P6 requires sound insulation sufficient to prevent illness or loss of amenity. The base text gives no number. Compliance with Housing Provisions Part 10.7 satisfies H4P6. The Northern Territory replacement text requires walls separating dwellings to have DnT,w + Ctr not less than 45, measured in situ under AS/NZS ISO 717.1. Walls between wet areas and habitable rooms of an adjoining dwelling must resist impact-generated sound sufficiently to prevent illness or loss of amenity, with no numeric impact rating given. Pipes and service elements must not compromise wall insulation. ncc.abcb.gov.au/editions/ncc-2022/adopted/volume-two/h-class-1-and-10-buildings/part-h4-health-and-amenity

Figures are as published by the sources above at their respective dates and are paraphrased summaries, not verbatim reproductions. Verify current pricing and rules directly with builders, lenders and planning authorities.